Submersible Cable

JACCO 3 core flat submersible cables are manufactured keeping in mind the severe and difficult conditions in which they are required to perform. Submersible cables are used for submersible pumps in deep well. Jacco submersible cables are manufactured keeping in mind the hostile environment of installation of the cable in which they have to be performed.

Conductor

Each cable is manufactured with electrolytic grade bright annealed bare copper conductor, uniformly bunched to ensure flexibility and uniform resistance, which also helps in saving electricity.

Insulation

The cable is insulated with specially formulated superior grade of PVC compound which offers high insulation resistance and necessary electrical strength. The insulation is resistance to moisture, oils, etc giving long life and electrical safety.

Sheath

The cores are laid up in flat parallel position. The outer sheath of the cable is made from a special grade of abrasion resistance PVC compound resistant to water, alkalies, moisture, etc.

Quality Assurance

High quality standards are built into every 'JACCO' product. Rigid tests and checks at every stage, from raw material through manufacturing stages and finally upto the finished product ensure that JACCO Cables meet customer satisfaction.

Packing

The above cables are supplied in coils of 90Mtrs. Length or wooden drum of 500 Mtrs.

3 Core Flat Cables as per IS:694:1990
Conductor Insulation Sheath Overall dimensions Resistance at 20°C (max.) Ohm/Km Current Carrying capacity @ 40°C Amps
Area Sq.mm Number/Size of wire mm Thickness mm Core Dia mm Thickness mm Overall Width mm Overall Thickness Mm
1.5 22/0.3 0.8 3.24 1.15 12.8 6.0 12.10 14
2.5 36/0.3 0.9 3.85 1.15 14.6 6.4 7.41 18
4.0 56/0.3 1.0 4.60 1.15 17.2 7.4 4.95 26
6.0 84/0.3 1.0 5.10 1.15 18.7 7.9 3.30 31
10 140/0.3 1.0 6.60 1.40 23.7 9.9 1.91 42
16 226/0.3 1.0 8.00 1.40 28.0 11.4 1.21 57

 

Selection Guide for 3 Core Flat Submersible Cables
1) HP Vs Current: The full load current for submersible pump motors, 3 phase, 50 cycles, 440 Volts.
Hp 5.0 7.5 10.0 12.5 15.0 17.5 20.0 25.0 30.0 35.0 40.0 45.0 50.0 55.0 60.0 65.0 70.0 75.0 80.0
Amp 7.5 11.0 14.9 18.9 22.5 25.2 28.4 35.6 42.3 50.4 58.1 62.1 67.5 73.8 81.0 87.3 93.6 100.80 108.0
2) Derating Factors: Multiply the current carrying capacity of the cable by factors given below for various ambient temperatures.
Ambient Temperature °C 30 35 40 45 50
derating Factor 1.09 1.04 1.00 0.95 0.77

For complete details refer to our brochure

Dislcaimer:

All the information given here is in good faith. Jacco Cables Pvt Ltd will not be liable for any kind of damages arising out of incorrect usage or interpretation.